SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 2 DO HIGH FEATURE 24V DC, 15 MM WIDTH DIAGNOSIS F. SHORT-CIRCUIT AND OPEN-CIRCUIT, FIRST-UP SIGNAL WITH LED SF (GROUP FAULT), 5 PIECES PER PACKAGING UNIT | 
| Supply voltage | 
| Reverse voltage protection | 
Yes; when using the same load voltage as on the power module | 
| Load voltage L+ | 
| ● Rated value (DC) | 
24 V; From power module | 
| ● Reverse polarity protection | 
Yes; polarity reversal can lead to the digital outputs being connected through | 
| Input current | 
| from load voltage L+ (without load), max. | 
5 mA; Per channel | 
| from backplane bus 3.3 V DC, max. | 
10 mA | 
| Power loss | 
| Power loss, typ. | 
0.4 W | 
| Address area | 
| Address space per module | 
| ● with packing | 
2 bit | 
| ● without packing | 
1 byte | 
| Digital outputs | 
| Number of digital outputs | 
2 | 
| Short-circuit protection | 
Yes | 
| ● Response threshold, typ. | 
1,5 A | 
| Limitation of inductive shutdown voltage to | 
-55 to -60 V, typ. L+( ) | 
| Controlling a digital input | 
Yes | 
| Switching capacity of the outputs | 
| ● Lamp load, max. | 
2.5 W | 
| Load resistance range | 
| ● lower limit | 
48 Ω | 
| ● upper limit | 
3 400 Ω | 
| Output voltage | 
| ● for signal "1", min. | 
L+ (-1 V) | 
| Output current | 
| ● for signal "1" rated value | 
0.5 A | 
| ● for signal "1" permissible range for 0 to 60 °C, min. | 
7 mA | 
| ● for signal "1" permissible range for 0 to 60 °C, max. | 
600 mA | 
| ● for signal "0" residual current, max. | 
0.3 mA | 
| Output delay with resistive load | 
| ● "0" to "1", max. | 
100 µs | 
| ● "1" to "0", max. | 
400 µs | 
| Parallel switching of 2 outputs | 
| ● for uprating | 
No | 
| ● for redundant control of a load | 
Yes; per module | 
| Switching frequency | 
| ● with resistive load, max. | 
100 Hz | 
| ● with inductive load, max. | 
2 Hz | 
| ● on lamp load, max. | 
10 Hz | 
| Total current of the outputs (per group) | 
| all mounting positions | 
| — up to 60 °C, max. | 
1 A | 
| Cable length | 
| ● Cable length, shielded, max. | 
1 000 m | 
| ● Cable length unshielded, max. | 
600 m | 
| Isochronous mode | 
| Isochronous mode (application synchronized up to terminal) | 
Yes | 
| Interrupts/diagnostics/status information | 
| Substitute values connectable | 
Yes; 0/1 | 
| Diagnostic messages | 
| ● Diagnostic functions | 
Yes; Can be read out | 
| ● Wire-break | 
Yes; channel by channel | 
| ● Short-circuit | 
Yes; channel by channel | 
| Diagnostics indication LED | 
| ● Group error SF (red) | 
Yes | 
| ● Status indicator digital output (green) | 
Yes | 
| Parameter | 
| Remark | 
3 byte | 
| Diagnostics wire break | 
Disable / enable | 
| Diagnostics short-circuit | 
Disable / enable | 
| Behavior on CPU/master STOP, channel-wise | 
Substitute a value/keep last value | 
| Galvanic isolation | 
| Galvanic isolation digital outputs | 
| ● between the channels | 
No | 
| ● between the channels and the backplane bus | 
Yes | 
| Isolation | 
| Isolation tested with | 
500 V DC | 
| Dimensions | 
| Width | 
15 mm | 
| Height | 
81 mm | 
| Depth | 
52 mm | 
| Weights | 
| Weight, approx. | 
40 g | 
| last modified: | 