 SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 4 DO SHIGH FEATURE 24V/2A DC, 15 MM WIDTH DIAGNOSIS SHORT CIRCUIT, SF-LED 5 PIECES PER PACKAGING UNIT  | 
 | 
| Supply voltage | 
| Reverse voltage protection | 
Yes; when using the same load voltage as on the power module | 
| Load voltage L+ | 
| Rated value (DC) | 
24 V; From power module | 
| Reverse polarity protection | 
Yes; polarity reversal can lead to the digital outputs being connected through | 
| Input current | 
| from load voltage L+ (without load), max. | 
5 mA; Per channel | 
| from backplane bus 3.3 V DC, max. | 
10 mA | 
| Power losses | 
| Power loss, typ. | 
1.6 W | 
| Address area | 
| Address space per module | 
| with packing | 
4 bit | 
| without packing | 
1 byte | 
| Digital outputs | 
| Number of digital outputs | 
4 | 
| Short-circuit protection | 
Yes | 
| Response threshold, typ. | 
5 to 10 A | 
| Limitation of inductive shutdown voltage to | 
L+ -(37 to 41V) | 
| Controlling a digital input | 
Yes | 
| Load resistance range | 
| lower limit | 
12 Ω | 
| upper limit | 
3400 Ω | 
| Output voltage | 
| for signal "1", min. | 
L+ (-1.0 V) | 
| Output current | 
| for signal "1" rated value | 
2 A | 
| for signal "1" permissible range for 0 to 60 °C, min. | 
7 mA | 
| for signal "1" permissible range for 0 to 60 °C, max. | 
2.4 A | 
| for signal "0" residual current, max. | 
0.5 mA | 
| Output delay with resistive load | 
| "0" to "1", max. | 
250 µs | 
| "1" to "0", max. | 
400 µs | 
| Parallel switching of 2 outputs | 
| for increased power | 
No | 
| for redundant control of a load | 
Yes; per module | 
| Switching frequency | 
| with resistive load, max. | 
100 Hz | 
| with inductive load, max. | 
2 Hz | 
| on lamp load, max. | 
10 Hz | 
| Aggregate current of outputs (per group) | 
| horizontal installation | 
| up to 60 °C, max. | 
4 A | 
| vertical installation | 
| up to 40 °C, max. | 
4 A; At 55 °C and 24 V DC | 
| Cable length | 
| Cable length, shielded, max. | 
1000 m | 
| Cable length unshielded, max. | 
600 m | 
| Isochronous mode | 
| Isochronous operation (application synchronized up to terminal) | 
Yes | 
| Interrupts/diagnostics/status information | 
| Diagnostic messages | 
| Diagnostic functions | 
Yes | 
| Short circuit | 
Yes; Module-wise | 
| Diagnostics indication LED | 
| Group error SF (red) | 
Yes; SF-LED (red) | 
| Status indicator digital output (green) | 
Yes; Per channel | 
| Galvanic isolation | 
| Galvanic isolation digital outputs | 
| between the channels | 
No | 
| between the channels and the backplane bus | 
Yes | 
| Isolation | 
| Isolation checked with | 
500 V DC | 
| Dimensions | 
| Width | 
15 mm | 
| Height | 
81 mm | 
| Depth | 
52 mm | 
| Weights | 
| Weight, approx. | 
40 g | 
| Status | 
May 14, 2014 |