 SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 2 DO 24...230V AC, 15 MM WIDTH 5 PIECES PER PACKAGING UNIT  | 
 | 
| Supply voltage | 
| Reverse voltage protection | 
Yes; when using the same load voltage as on the power module | 
| Load voltage L1 | 
| permissible range, lower limit (AC) | 
24 V; From power module | 
| permissible range, upper limit (AC) | 
230 V | 
| Input current | 
| from load voltage L+ (without load), max. | 
30 mA | 
| from backplane bus 3.3 V DC, max. | 
18 mA | 
| Power loss | 
| Power loss, typ. | 
4 W | 
| Address area | 
| Address space per module | 
| with packing | 
2 bit | 
| without packing | 
1 byte | 
| Digital outputs | 
| Number of digital outputs | 
2 | 
| Short-circuit protection | 
Yes | 
| Limitation of inductive shutdown voltage to | 
-55 to -60 V | 
| Controlling a digital input | 
Yes; possible | 
| Switching capacity of the outputs | 
| Lamp load, max. | 
100 W | 
| Output voltage | 
| for signal "1", min. | 
L+ (-1.5 V) | 
| Output current | 
| for signal "1" rated value | 
2 A | 
| for signal "1" permissible range for 0 to 60 °C, min. | 
0.1 mA | 
| for signal "1" permissible range for 0 to 60 °C, max. | 
2.2 A | 
| for signal "0" residual current, max. | 
3 mA | 
| Output delay with resistive load | 
| "0" to "1", max. | 
15 ms | 
| "1" to "0", max. | 
15 ms | 
| Parallel switching of 2 outputs | 
| for uprating | 
No | 
| for redundant control of a load | 
Yes; per module | 
| Switching frequency | 
| with resistive load, max. | 
10 Hz | 
| with inductive load, max. | 
0.5 Hz | 
| on lamp load, max. | 
1 Hz | 
| Total current of the outputs (per group) | 
| all mounting positions | 
| up to 40 °C, max. | 
2 A | 
| up to 50 °C, max. | 
1.5 A | 
| up to 60 °C, max. | 
1 A | 
| Cable length | 
| Cable length, shielded, max. | 
1000 m | 
| Cable length unshielded, max. | 
600 m | 
| Interrupts/diagnostics/status information | 
| Diagnostic messages | 
| Diagnostic functions | 
No | 
| Diagnostics indication LED | 
| Status indicator digital output (green) | 
Yes | 
| Parameter | 
| Remark | 
3 byte | 
| Behavior on CPU/master STOP, channel-wise | 
Substitute a value/keep last value, 0/1 | 
| Galvanic isolation | 
| Galvanic isolation digital outputs | 
| between the channels | 
No | 
| between the channels and the backplane bus | 
Yes | 
| Isolation | 
| Isolation tested with | 
2500 V DC | 
| Dimensions | 
| Width | 
15 mm | 
| Height | 
81 mm | 
| Depth | 
52 mm | 
| Weights | 
| Weight, approx. | 
37 g | 
| Status | 
Jul 7, 2014 |