| Supply voltage | 
| Load voltage L+ | 
| ● Rated value (DC) | 
24 V | 
| ● Reverse polarity protection | 
Yes | 
| Input current | 
| from load voltage L+ (without load), max. | 
80 mA | 
| from backplane bus 3.3 V DC, max. | 
10 mA | 
| Power losses | 
| Power loss, typ. | 
1.9 W | 
| Address area | 
| Address space per module | 
| ● Address space per module, max. | 
4 byte | 
| Analog inputs | 
| Number of analog inputs | 
2 | 
| permissible input voltage for voltage input (destruction limit), max. | 
35 V | 
| Cycle time (all channels) max. | 
250 µs | 
| Input ranges | 
| ● Voltage | 
Yes | 
| ● Current | 
No | 
| ● Thermocouple | 
No | 
| ● Resistance thermometer | 
No | 
| ● Resistance | 
No | 
| Input ranges (rated values), voltages | 
| ● 1 to 5 V | 
Yes | 
| ● Input resistance (1 to 5 V) | 
120 kΩ | 
| ● -10 V to +10 V | 
Yes | 
| ● Input resistance (-10 V to +10 V) | 
120 kΩ | 
| ● -2.5 V to +2.5 V | 
Yes | 
| ● Input resistance (-2.5 V to +2.5 V) | 
120 kΩ | 
| ● -5 V to +5 V | 
Yes | 
| ● Input resistance (-5 V to +5 V) | 
120 kΩ | 
| Cable length | 
| ● Cable length, shielded, max. | 
200 m | 
| Analog value creation | 
| Integration and conversion time/resolution per channel | 
| ● Resolution with overrange (bit including sign), max. | 
16 bit | 
| Smoothing of measured values | 
| ● Parameterizable | 
Yes | 
| ● Step: None | 
Yes | 
| ● Step: low | 
Yes | 
| ● Step: Medium | 
Yes | 
| ● Step: High | 
Yes | 
| Encoder | 
| Connection of signal encoders | 
| ● for voltage measurement | 
Yes | 
| Errors/accuracies | 
| Linearity error (relative to input range), (+/-) | 
0.03 % | 
| Temperature error (relative to input range), (+/-) | 
0.01 %/K | 
| Crosstalk between the inputs, min. | 
-50 dB | 
| Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) | 
0.1 % | 
| Operational limit in overall temperature range | 
| ● Voltage, relative to input area, (+/-) | 
0.3 % | 
| Basic error limit (operational limit at 25 °C) | 
| ● Voltage, relative to input area, (+/-) | 
0.2 % | 
| Isochronous mode | 
| Isochronous operation (application synchronized up to terminal) | 
Yes | 
| Interrupts/diagnostics/status information | 
| Alarms | 
| ● Hardware interrupt | 
Yes | 
| Diagnostic messages | 
| ● Diagnostic functions | 
Yes | 
| ● Diagnostic information readable | 
Yes | 
| ● Wire break | 
Yes | 
| ● Group error | 
Yes | 
| ● Overflow/underflow | 
Yes | 
| Diagnostics indication LED | 
| ● Group error SF (red) | 
Yes | 
| Galvanic isolation | 
| Galvanic isolation analog inputs | 
| ● between the channels | 
No | 
| ● between the channels and the backplane bus | 
Yes | 
| ● between the channels and the load voltage L+ | 
Yes | 
| Dimensions | 
| Width | 
15 mm | 
| Height | 
81 mm | 
| Depth | 
52 mm | 
| Weights | 
| Weight, approx. | 
45 g | 
| last modified: | 