SIMATIC DP, ET 200ECO PN, 8 DI 24V DC; 8 X M12, DEGREE OF PROTECTION IP67 | 
| General information | 
| Vendor identification (VendorID) | 
002AH | 
| Device identifier (DeviceID) | 
0306H | 
| Supply voltage | 
| 24 V DC | 
Yes | 
| permissible range, lower limit (DC) | 
20.4 V | 
| permissible range, upper limit (DC) | 
28.8 V | 
| Reverse polarity protection | 
Yes | 
| Input current | 
| Current consumption, typ. | 
100 mA | 
| Encoder supply | 
| Number of outputs | 
8 | 
| Output current | 
| ● Output current, rated value | 
100 mA; per output | 
| 24 V encoder supply | 
| ● Short-circuit protection | 
Yes | 
| Power loss | 
| Power loss, typ. | 
4.5 W | 
| Digital inputs | 
| Number of digital inputs | 
8 | 
| ● in groups of | 
1 | 
| Input characteristic curve in accordance with IEC 61131, type 3 | 
Yes | 
| Number of simultaneously controllable inputs | 
| all mounting positions | 
| — up to 60 °C, max. | 
8 | 
| Input voltage | 
| ● Type of input voltage | 
DC | 
| ● Rated value, DC | 
24 V | 
| Input current | 
| ● for signal "0", max. (permissible quiescent current) | 
1.5 mA | 
| ● for signal "1", typ. | 
7 mA | 
| Input delay (for rated value of input voltage) | 
| for standard inputs | 
| — at "0" to "1", max. | 
typically 3 ms | 
| — at "1" to "0", max. | 
typically 3 ms | 
| Cable length | 
| ● Cable length unshielded, max. | 
30 m | 
| Interfaces | 
| Transmission procedure | 
100BASE-TX | 
| Transmission rate, max. | 
100 Mbit/s | 
| PROFINET IO | 
| ● Number of PROFINET interfaces | 
1 | 
| ● Autocrossing | 
Yes | 
| ● automatic detection of transmission rate | 
Yes | 
| ● integrated switch | 
Yes | 
| PROFINET IO Device | 
| — IRT with the option "high flexibility", supported | 
Yes | 
| — Prioritized startup | 
Yes | 
| Protocols | 
| PROFINET IO | 
Yes | 
| PROFINET CBA | 
No | 
| PROFIsafe | 
No | 
| Protocols (Ethernet) | 
| ● SNMP | 
Yes | 
| ● DCP | 
Yes | 
| ● LLDP | 
Yes | 
| ● ping | 
Yes | 
| ● ARP | 
Yes | 
| Interrupts/diagnostics/status information | 
| Status indicator | 
Yes; Green LED | 
| Alarms | 
| ● Diagnostic alarm | 
Yes | 
| Diagnostic messages | 
| ● Diagnostic functions | 
Yes | 
| ● Diagnostic information readable | 
Yes | 
| ● Monitoring the supply voltage | 
Yes; Green "ON" LED | 
| ● Wire-break in signal transmitter cable | 
Yes | 
| ● Short-circuit encoder supply | 
Yes; Per channel group | 
| ● Group error | 
Yes; Red/yellow "SF/MT" LED | 
| Galvanic isolation | 
| between the load voltages | 
Yes | 
| between load voltage and all other switching components | 
No | 
| between Ethernet and electronics | 
Yes | 
| Galvanic isolation digital inputs | 
| ● between the channels | 
No | 
| Permissible potential difference | 
| between different circuits | 
75 VDC / 60 VAC | 
| Isolation | 
| tested with | 
| ● 24 V DC circuits | 
500 V | 
| ● Interface | 
1 500 V; According to IEEE 802.3 | 
| Degree and class of protection | 
| IP65 | 
Yes | 
| IP66 | 
Yes | 
| IP67 | 
Yes | 
| Connection method | 
| M12 | 
Yes | 
| Dimensions | 
| Width | 
60 mm | 
| Height | 
175 mm | 
| Depth | 
49 mm | 
| Weights | 
| Weight (without packaging) | 
910 g | 
| last modified: | 