 SIMATIC DP, ET 200ECO PN, 8 DO 24V DC/1,3A; 8 X M12, DEGREE OF PROTECTION IP67  | 
 | 
| General information | 
| Vendor identification (VendorID) | 
002AH | 
| Device identifier (DeviceID) | 
0306H | 
| Supply voltage | 
| Load voltage 1L+ | 
| Rated value (DC) | 
24 V | 
| permissible range, lower limit (DC) | 
20.4 V | 
| permissible range, upper limit (DC) | 
28.8 V | 
| Reverse polarity protection | 
Yes | 
| Load voltage 2L+ | 
| Rated value (DC) | 
24 V | 
| permissible range, lower limit (DC) | 
20.4 V | 
| permissible range, upper limit (DC) | 
28.8 V | 
| Reverse polarity protection | 
Yes | 
| Input current | 
| from load voltage 1L+ (unswitched voltage) | 
4 A | 
| from load voltage 2L+, max. | 
4 A | 
| Power losses | 
| Power loss, typ. | 
5.5 W | 
| Digital outputs | 
| Number of digital outputs | 
8 | 
| In groups of | 
4 | 
| Short-circuit protection | 
Yes | 
| Response threshold, typ. | 
1,8 A | 
| Limitation of inductive shutdown voltage to | 
Typ. (L1+, L2+) -47 V | 
| Controlling a digital input | 
Yes | 
| Switching capacity of the outputs | 
| on lamp load, max. | 
5 W | 
| Output current | 
| for signal "1" rated value | 
1.3 A; Maximum | 
| for signal "0" residual current, max. | 
1.5 mA | 
| Parallel switching of 2 outputs | 
| for increased power | 
No | 
| for redundant control of a load | 
Yes | 
| Switching frequency | 
| with resistive load, max. | 
100 Hz | 
| with inductive load, max. | 
0.5 Hz | 
| on lamp load, max. | 
1 Hz | 
| Aggregate current of outputs (per group) | 
| all mounting positions | 
| up to 60 °C, max. | 
3.9 A | 
| Cable length | 
| Cable length unshielded, max. | 
30 m | 
| Interfaces | 
| Transmission procedure | 
100BASE-TX | 
| Transmission rate, max. | 
100 Mbit/s | 
| Supports protocol for PROFINET IO | 
| Number of PROFINET interfaces | 
1 | 
| Autocrossing | 
Yes | 
| Automatic detection of transmission speed | 
Yes | 
| Integrated switch | 
Yes | 
| PROFINET IO Device | 
| IRT with the option "high flexibility" supported | 
Yes | 
| Prioritized startup | 
Yes | 
| Protocols | 
| Supports protocol for PROFINET IO | 
Yes | 
| PROFINET CBA | 
No | 
| Supports protocol for PROFIsafe | 
No | 
| Protocols (Ethernet) | 
| SNMP | 
Yes | 
| DCP | 
Yes | 
| LLDP | 
Yes | 
| ping | 
Yes | 
| ARP | 
Yes | 
| Interrupts/diagnostics/status information | 
| Status indicator | 
Yes; Green LED | 
| Alarms | 
| Diagnostic alarm | 
Yes | 
| Diagnostic messages | 
| Diagnostic functions | 
Yes | 
| Diagnostic information readable | 
Yes | 
| Monitoring the supply voltage | 
Yes; Green "ON" LED | 
| Wire break in actuator cable | 
Yes | 
| Short circuit | 
Yes | 
| Group error | 
Yes; Red/yellow "SF/MT" LED | 
| Galvanic isolation | 
| between the load voltages | 
Yes | 
| between load voltage and all other switching components | 
No | 
| between Ethernet and electronics | 
Yes | 
| Galvanic isolation digital outputs | 
| between the channels | 
No | 
| Permissible potential difference | 
| between different circuits | 
75 VDC / 60 VAC | 
| Isolation | 
| tested with | 
| 24 V DC circuits | 
500 V | 
| Interface | 
1500 V; According to IEEE 802.3 | 
| Degree and class of protection | 
| IP65 | 
Yes | 
| IP66 | 
Yes | 
| IP67 | 
Yes | 
| Connection method | 
| M12 | 
Yes | 
| Dimensions | 
| Width | 
60 mm | 
| Height | 
175 mm | 
| Depth | 
49 mm | 
| Weights | 
| Weight (without packaging) | 
910 g | 
| Status | 